AI Speeds Renewable Grid Recovery but Communication Delays Can Trigger Instability

Ilustrasi By AI

FORMOSA NEWS - Jakarta - Artificial intelligence can significantly accelerate the recovery of renewable-energy power networks after disturbances, but its benefits can deteriorate when communication between distributed controllers becomes too slow, according to research by Diah Widiastuti of Universitas Nasional and Titi Ratnasari of Institut Teknologi PLN, published in the Formosa Journal of Science and Technology in 2026. Their simulations show that AI-based frequency stabilization reduced average recovery time by 22.32 percent under normal communication conditions, while high communication latency combined with renewable penetration above 70 percent caused a sharp decline in system coherence and autonomous recovery capacity.

Renewable Energy Creates New Challenges for Grid Stability

The growing use of solar panels, wind turbines, and battery storage is changing how electricity networks respond to disturbances. Unlike conventional generators, many renewable-energy resources connect to the grid through power-electronic inverters and therefore do not provide the same natural rotational inertia as traditional synchronous generators.

As renewable penetration increases, small changes in electricity supply or demand can produce faster frequency deviations. This makes the role of inverter controls, batteries, digital controllers, and communication networks increasingly important for maintaining grid stability. The challenge is particularly significant in isolated or islanded electricity systems, where there is less support from interconnected grids.

Artificial intelligence offers a potential solution. AI-based control systems can adapt their responses to changing renewable output, electricity demand, battery conditions, and other operating variables. However, Diah Widiastuti and Titi Ratnasari point out that distributed AI controllers must work collectively. If communication between controllers is delayed, different parts of the grid may respond at different times.

The researchers describe this phenomenon as “collective frequency desynchronization” a condition in which inverter clusters lose coordinated frequency responses even though the overall system frequency may appear to recover.

Digital Twin Tests 1,500 Disturbance Scenarios

Widiastuti and Ratnasari examined the problem using a calibrated digital-twin simulation of a representative islanded 20-kV hybrid renewable distribution network in East Nusa Tenggara, Indonesia.

The simulated system included:

  • 8.5 MWp of solar photovoltaic generation;
  • 2.4 MW of wind generation;
  • a 4 MW/16 MWh battery energy-storage system;
  • 18 distribution buses; and
  • a peak electricity demand of 10.2 MW.

The model was calibrated using 30 days of operational profiles covering renewable-energy output, feeder load, battery state of charge, inverter response, and local frequency measurements. Researchers then subjected the virtual network to 1,500 dynamic disturbance scenarios, including sudden solar and wind changes, load fluctuations, battery limitations, inverter-response mismatches, and communication delays.

The AI-based controller was compared with conventional droop-based control. The researchers evaluated recovery time, frequency nadir, rate of change of frequency, frequency coherence, battery reserves, load continuity, and an Autonomous Recovery Capacity Index, or ARCI.

AI Makes Frequency Recovery Faster

Under normal communication conditions, the AI-based system performed better than conventional droop control.

The average frequency recovery time fell from 11.2 seconds to 8.7 seconds, representing a 22.32 percent improvement. The frequency nadir also improved from 49.77 Hz to 49.89 Hz, while the maximum rate of change of frequency improved from -0.41 Hz/s to -0.29 Hz/s.

The improvement extended beyond recovery speed. The frequency coherence score increased from 0.82 with baseline droop control to 0.94 with AI stabilization. A higher score indicates that different parts of the network recover frequency in a more coordinated manner.

The results suggest that AI can coordinate battery support and inverter responses more effectively when communication conditions are reliable.

Communication Latency Can Reverse the Benefit

The researchers found a major weakness when high renewable penetration was combined with communication delays.

When renewable penetration exceeded 70 percent and communication latency surpassed 200 milliseconds, average recovery time increased to 13.9 seconds. The frequency coherence score fell dramatically to 0.58, compared with 0.94 under normal-latency AI control.

In these conditions, inverter clusters could receive information and execute corrective actions at different times. The result was collective frequency desynchronization: the average system frequency could move back toward normal while individual sections of the network remained dynamically out of sync.

This distinction is important because monitoring only the average frequency could conceal instability occurring at individual buses or inverter clusters.

The same problem appeared in the Autonomous Recovery Capacity Index. Under baseline droop control, ARCI was 0.77. AI stabilization increased it to 0.86 under normal latency, but the index dropped to 0.64 under high-latency conditions.

The scenario classification produced a similar warning. AI control reduced desynchronized recovery cases from 105 to 29 under normal communication conditions. Under high-latency stress, however, the number increased to 277 scenarios.

What the Findings Mean for Renewable Grids

For Widiastuti of Universitas Nasional and Ratnasari of Institut Teknologi PLN, the findings indicate that AI should not be treated as a standalone solution for renewable-grid stability. Its effectiveness depends on whether distributed controllers can exchange information quickly enough and maintain coordinated responses.

An ethical paraphrase of their central finding is that AI can strengthen autonomous grid recovery when communication is reliable, but delayed coordination can weaken or even reverse those gains by reducing frequency coherence.

The researchers recommend three practical measures. First, AI-based grid controllers should incorporate communication-latency tolerance thresholds. Second, grid operators should monitor frequency dispersion at individual buses rather than relying only on system-wide frequency. Third, control systems should have fallback mechanisms, allowing local droop control, battery support, or predefined emergency responses to take over when communication becomes unreliable.

These safeguards could become increasingly important as renewable penetration grows and electricity systems depend more heavily on inverter-based resources and digital control.

Results Remain Simulation-Based

The researchers caution that the 70 percent renewable-penetration level and 200-millisecond communication threshold are specific to the simulated system and should not be interpreted as universal limits. The model does not fully reproduce a particular utility network and simplifies electromagnetic transients, harmonics, cyberattacks, and detailed inverter-protection behavior.

The AI controller also remains untested in an operational power network. The authors recommend further validation through real-time digital simulation, hardware-in-the-loop testing, communication-network modeling, cyber-resilience scenarios, and field implementation.

About the Researchers

Diah Widiastuti is affiliated with Universitas Nasional, while Titi Ratnasari is affiliated with Institut Teknologi PLN. Their article addresses artificial-intelligence-based control, renewable-energy networks, frequency stability, autonomous grid recovery, inverter-based resources, and battery energy storage. The PDF does not state the authors’ academic degrees or specific departmental fields, so those details cannot be reliably added without additional biographical sources.

Source

Article title listed in the PDF: Student Experiences in Developing Self-Directed Learning Within Technology-Based Learning Systems in Higher Education
Journal: Formosa Journal of Science and Technology (FJST)
Publication: Volume 5, No. 8, 2026, pp. 2353–2374
Authors: Diah Widiastuti and Titi Ratnasari
DOI: 10.55927/fjst.v5i8.132

URL : https://journalfjst.my.id/index.php/fjst

Posting Komentar

0 Komentar